2.14 Impedance Protection (ANSI 21)
101
7UM61 Manual
C53000-G1176-C127-3
2.14.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.14.4 Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
3301
IMPEDANCE PROT.
OFF
ON
Block relay
OFF
Impedance Protection
3302
IMP I>
1A
0.10 .. 20.00 A
1.35 A
Fault Detection I> Pickup
5A
0.50 .. 100.00 A
6.75 A
3303
U< SEAL-IN
ON
OFF
OFF
State of Undervoltage
Seal-in
3304
U<
10.0 .. 125.0 V
80.0 V
Undervoltage Seal-in
Pickup
3305
T-SEAL-IN
0.10 .. 60.00 sec
4.00 sec
Duration of Undervoltage
Seal-in
3306
ZONE Z1
1A
0.05 .. 130.00
Ω
2.90
Ω
Impedance Zone Z1
5A
0.01 .. 26.00
Ω
0.58
Ω
3307
T-Z1
0.00 .. 60.00 sec;
∞
0.10 sec
Impedance Zone Z1 Time
Delay
3308
ZONE Z1B
1A
0.05 .. 65.00
Ω
4.95
Ω
Impedance Zone Z1B
5A
0.01 .. 13.00
Ω
0.99
Ω
3309
T-Z1B
0.00 .. 60.00 sec;
∞
0.10 sec
Impedance Zone Z1B
Time Delay
3310
ZONE Z2
1A
0.05 .. 65.00
Ω
4.15
Ω
Impedanz Zone Z2
5A
0.01 .. 13.00
Ω
0.83
Ω
3311
ZONE2 T2
0.00 .. 60.00 sec;
∞
0.50 sec
Impedance Zone Z2 Time
Delay
3312
T END
0.00 .. 60.00 sec;
∞
3.00 sec
T END: Final Time Delay
No.
Information
Type of In-
formation
Comments
3953
>Imp. BLOCK
EM
>BLOCK impedance protection
3956
>Extens. Z1B
EM
>Zone 1B extension for impedance prot.
3958
>Useal-in BLK
EM
>Imp. prot. : BLOCK undervoltage seal-in
3961
Imp. OFF
AM
Impedance protection is switched OFF
3962
Imp. BLOCKED
AM
Impedance protection is BLOCKED
3963
Imp. ACTIVE
AM
Impedance protection is ACTIVE
3966
Imp. picked up
AM
Impedance protection picked up
3967
Imp. Fault L1
AM
Imp.: Fault detection , phase L1
3968
Imp. Fault L2
AM
Imp.: Fault detection , phase L2
3969
Imp. Fault L3
AM
Imp.: Fault detection , phase L3
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...