4.13 Overexcitation (Volt/Hertz) Protection (ANSI 24)
327
7UM61 Manual
C53000-G1176-C127-3
Influencing Variables
Figure 4-6
Resulting Tripping Characteristic from Thermal Replica and Stage Characteris-
tic of the Overexcitation Protection (Default Setting)
Auxiliary DC voltage in range
0.8
≤
U
Aux
/U
AuxN
≤
1.15
≤
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
≤
0.5 % / 10 K
Harmonics
– Up to 10 % 3rd harmonic
– Up to 10 % 5th harmonic
≤
1 %
≤
1 %
www
. ElectricalPartManuals
. com