2 Functions
32
7UM61 Manual
C53000-G1176-C127-3
Parameter
104
FAULT VALUE
is used to specify whether the oscillographic fault re-
cording should record
Instant. values
or
RMS values
. If
RMS values
is stored,
the available recording time increases by the factor 16.
For the high-current stage I>> of the overcurrent protection, address
113
O/C PROT.
I>>
determines whether
Non-Directional
or
directional
is to be operative. By
selecting
Disabled
, this overcurrent stage can be excluded altogether. With inverse
time overcurrent protection
114
O/C PROT. Ip
, depending on the ordered variant,
various characteristics are available for selection, in accordance with IEC or ANSI
standard. Selecting 'disabled' deconfigures inverse time overcurrent protection.
For earth fault protection, Address
150
S/E/F PROT.
presents the options
non-
dir. U0
,
non-dir. U0&I0
and
directional
, unless the whole function is
Disabled
. The first option evaluates only the displacement voltage (to be used with
unit connection). The second option evaluates in addition to the displacement voltage,
the magnitude of the earth fault current (or the difference between the starpoint current
and the total current of a toroidal CT in busbar systems with low-ohmic switchable star-
point resistors). The third option considers as a further criterion the direction of the
earth fault current if with machines in busbar connection the magnitudes of displace-
ment voltage and earth fault current alone are not sufficient to distinguish between
system earth faults and machine earth faults.
For trip circuit monitoring, address
182
Trip Cir. Sup.
is used to specify whether
two binary inputs (
2 Binary Inputs
) or only one (
1 Binary Input
) should be
utilized.
2.2.3
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
103
Grp Chge OPTION
Disabled
Enabled
Disabled
Setting Group Change Option
104
FAULT VALUE
Disabled
Instant. values
RMS values
Instant. values
Fault values
112
O/C PROT. I>
Disabled
Enabled
Enabled
Overcurrent Protection I>
113
O/C PROT. I>>
Disabled
directional
Non-Directional
Non-Directional
Overcurrent Protection I>>
114
O/C PROT. Ip
Disabled
with IEC
with ANSI
Disabled
Inverse O/C Time Protection
116
Therm.Overload
Disabled
Enabled
Enabled
Thermal Overload Protection
117
UNBALANCE LOAD
Disabled
Enabled
Enabled
Unbalance Load (Negative Se-
quence)
130
UNDEREXCIT.
Disabled
Enabled
Enabled
Underexcitation Protection
131
REVERSE POWER
Disabled
Enabled
Enabled
Reverse Power Protection
132
FORWARD POWER
Disabled
Enabled
Enabled
Forward Power Supervision
133
IMPEDANCE PROT.
Disabled
Enabled
Enabled
Impedance Protection
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...