2 Functions
38
7UM61 Manual
C53000-G1176-C127-3
2.3.3
Information List
273
STAR-POINT
low-resist.
high-resist.
high-resist.
Earthing of Machine Star-
point
274A
ATEX100
YES
NO
NO
Storage of th. Replicas w/o
Power Supply
276
TEMP. UNIT
Celsius
Fahrenheit
Celsius
Unit of temperature mea-
surement
280
TMin TRIP CMD
0.01 .. 32.00 sec
0.15 sec
Minimum TRIP Command
Duration
281
BkrClosed I MIN
1A
0.04 .. 1.00 A
0.04 A
Closed Breaker Min.
Current Threshold
5A
0.20 .. 5.00 A
0.20 A
No.
Information
Type of In-
formation
Comments
361
>FAIL:Feeder VT
EM
>Failure: Feeder VT (MCB tripped)
5002
Operat. Cond.
AM
Suitable measured quantities present
5145
>Reverse Rot.
EM
>Reverse Phase Rotation
5147
Rotation L1L2L3
AM
Phase Rotation L1L2L3
5148
Rotation L1L3L2
AM
Phase Rotation L1L3L2
Addr.
Parameter
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...