2.11 Underexcitation (Loss-of-Field) Protection (ANSI 40)
79
7UM61 Manual
C53000-G1176-C127-3
The following figure shows the logic diagram for underexcitation protection.
Figure 2-21
Logic diagram of the Underexcitation Protection
2.11.2 Setting Notes
General
The underexcitation protection is only effective and available if this function was set
during protective function configuration (Section 2.2, address
130
,
UNDEREXCIT.
is
set to
Enabled
. If the function is not required
Disabled
is set. The address
3001
UNDEREXCIT.
serves to enable the function
ON
and
OFF
or to block only the trip
command (
Block relay
).
The correct power system data input according to Section 2.3 is another prerequisite
for the parameterization of the underexcitation protection.