2 Functions
182
7UM61 Manual
C53000-G1176-C127-3
Example:
I
BI (HIGH)
1.8 mA (from the SIPROTEC
®
7UM61)
U
BI min
19 V for delivery setting for nominal voltages 24/48/60 V (for device
7UM61) 88 V for delivery setting for nominal voltages
110/125/220/250 V) (for device 7UM61)
U
Ctrl
110 V (system / trip circuit)
R
CBTC
500
Ω
(from power system / trip circuit)
U
CBTC (LOW)
2 V (system / trip circuit)
The closest standard value of 39 k
Ω
is selected; for the power:
2.29.3 Settings
2.29.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
8201
TRIP Cir. SUP.
OFF
ON
OFF
TRIP Circuit Supervision
No.
Information
Type of In-
formation
Comments
6851
>BLOCK TripC
EM
>BLOCK Trip circuit supervision
6852
>TripC trip rel
EM
>Trip circuit supervision: trip relay
6853
>TripC brk rel.
EM
>Trip circuit supervision: breaker relay
6861
TripC OFF
AM
Trip circuit supervision OFF
6862
TripC BLOCKED
AM
Trip circuit supervision is BLOCKED
6863
TripC ACTIVE
AM
Trip circuit supervision is ACTIVE
6864
TripC ProgFail
AM
Trip Circuit blk. Bin. input is not set
6865
FAIL: Trip cir.
AM
Failure Trip Circuit
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...