3 Mounting and Commissioning
242
7UM61 Manual
C53000-G1176-C127-3
For devices up to release 7UM61.../BB check the jumpers for the set nominal voltage
of the integrated power supply according to Table 3-1, the quiescent state of the life
contact according to Table 3-2 and the selected pickup voltages of the binary inputs
BI1 through BI7 according to Table 3-3.
Table 3-1
Jumper settings for nominal voltage of the integrated
power supply
on the pro-
cessor printed circuit board B–CPU for 7UM61.../BB
Table 3-2
Jumper setting for the quiescent state of the
life contact
on the B–CPU proces-
sor PCB for 7UM61.../BB
Table 3-3
Jumper settings for the
control voltages
of binary inputs BI1 through BI7 on the
B–CPU processor PCB for 7UM61.../BB
1)
Factory settings for devices with rated power supply voltages 24 VDC to 125 VDC
2)
Factory settings for devices with rated power supply voltages 110 VDC to 220 VDC and
115/230 VAC
Jumper
Rated voltage
60/110/125 VDC
110/125/220/250 V DC
115 V AC
24/48 VDC
X51
1–2 2–3
Jumpers
X51 to X53
Not used
X52
1–2 and 3–4
2–3
X53
1–2 2–3
interchangeable
cannot be changed
Jumper
Open in the quiescent
state
Closed in the quiescent
state
Presetting
X40
1–2
2–3
2–3
Binary Inputs
Jumper
19 V Threshold
88 V Threshold
BI1
X21
L
H
BI2
X22
L
H
BI3
X23
L
H
BI4
X24
L
H
BI5
X25
L
H
BI6
X26
L
H
BI7
X27
L
H
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...