![Siemens Siprotec 7UM611 Скачать руководство пользователя страница 68](http://html.mh-extra.com/html/siemens/siprotec-7um611/siprotec-7um611_manual_383128068.webp)
2 Functions
68
7UM61 Manual
C53000-G1176-C127-3
With a supposed load current of I = 1.5 · I
N, Device
and a preload I
pre
= 0, for different
ambient temperatures
Θ
K
the following trip times result
2.9.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
1601
Ther. OVER LOAD
OFF
ON
Block relay
Alarm Only
OFF
Thermal Overload Protec-
tion
1602
K-FACTOR
0.10 .. 4.00
1.11
K-Factor
1603
TIME CONSTANT
30 .. 32000 sec
600 sec
Thermal Time Constant
1604
Θ
ALARM
70 .. 100 %
90 %
Thermal Alarm Stage
1605
TEMP. RISE I
40 .. 200
°
C
100
°
C
Temperature Rise at
Rated Sec. Curr.
1606
TEMP. RISE I
104 .. 392
°
F
212
°
F
Temperature Rise at
Rated Sec. Curr.
1607
TEMP. INPUT
Disabled
Fieldbus
RTD 1
Disabled
Temperature Input
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...