2.32 RTD-Box
193
7UM61 Manual
C53000-G1176-C127-3
Figure 2-75
Logic Diagram for Temperature Processing
2.32.2 Setting Notes
General
The temperature detection function is only effective and accessible if it has been as-
signed to an interface during the configuration of the protection functions (Section
2.2). At address
190
RTD-BOX INPUT
the RTD-box(es) is allocated to the interface
at which it will be operated (e.g. port C). The number of sensor inputs and the commu-
nication mode were set at address
191
RTD CONNECTION
. The temperature unit (
°
C
or
°
F) was set in the Power System Data 1 at address
276
TEMP. UNIT
.
If the RTD-boxes operate in half duplex mode, it has to be selected for the Clear-to-
Send function (CTS) using plug-in jumpers (see Subsection 3.1.2) “/CTS triggered by
/RTS ” must be selected.
Device Settings
The settings are the same for each input and are here shown at the example of mea-
suring input 1.
Set the type of temperature detector for RTD 1 (temperature sensor for measuring
point 1) at address
9011
RTD 1 TYPE
. You can choose between
Pt 100
Ω
,
Ni 120
Ω
and
Ni 100
Ω
. If no temperature detector is available for RTD 1, set
RTD 1 TYPE
=
Not connected
. This setting is only possible via DIGSI
®
at "
Additional Settings
".
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...