![Siemens Siprotec 7UM611 Скачать руководство пользователя страница 184](http://html.mh-extra.com/html/siemens/siprotec-7um611/siprotec-7um611_manual_383128184.webp)
2 Functions
184
7UM61 Manual
C53000-G1176-C127-3
I0
(Zero sequence
current system)
I0/I
N,sec
· 100 %
The zero sequence current is determined
from the phase currents on the basis of the
definition equation for symmetrical compo-
nents. The calculation is performed once per
cycle.
I1
(Positive sequence
current system)
I1/I
N,sec
· 100 %
The positive sequence current is determined
from the phase currents on the basis of the
definition equation for symmetrical compo-
nents. The calculation is performed once per
cycle.
I2
(Negative sequence
current system)
I2/I
N,sec
· 100 %
The negative sequence current is determined
from the phase currents on the basis of the
definition equation for symmetrical compo-
nents. The calculation is performed once per
cycle.
ϕ
(Power angle)
ϕ
/180
°
· 100 %
The power angle is calculated from the posi-
tive sequence voltage and the positive se-
quence current. The following definition ap-
plies:
ϕ
=
ϕ
U -
ϕ
I (A positive angle will appear if the
current lags behind the voltage)
Measured Value
Scaling
Explanation
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...