2 Functions
174
7UM61 Manual
C53000-G1176-C127-3
2.28.2 Setting Notes
Measured Value
Monitoring
Measured value monitoring can be activated at address
8101
MEASURE. SUPERV
ON
or
OFF
. In addition the sensitivity of measured value monitorings can be modified.
Default values are set at the factory, which are sufficient in most cases. If especially
high operating asymmetries in currents and/or voltages is to be expected for the ap-
plication, or if it becomes apparent during operation that certain monitoring functions
activate sporadically, then the setting should be made less sensitive.
Address
8102
BALANCE U-LIMIT
determines the limit voltage (line–line), above
which voltage symmetry monitoring becomes effective (see also Voltage Symmetry
Monitoring figure)..
Address
8103
BAL. FACTOR U
is the associated symmetry factor; i.e. the slope of
the symmetry characteristic curve (see also Voltage Symmetry Monitoring figure).
Address
8104
BALANCE I LIMIT
determines the limit current, above which the
current symmetry monitor is effective (see also Current Symmetry Monitoring figure).
Address
8105
BAL. FACTOR I
is the associated symmetry factor; i.e. the slope of
the symmetry characteristic curve (see also Current Symmetry Monitoring figure).
Address
8106
Σ
I THRESHOLD
determines the limit current above which the current
sum monitor (see also Current Sum Monitoring figure) is activated (absolute portion,
only relative to IN). The relative portion (relative to the maximum conductor current)
for activating the current sum monitor is set at address
8107
Σ
I FACTOR
.
Address
8108
SUM.thres. U
determines the limit voltage above which current sum
monitoring becomes active (see also Current Sum Monitoring figure) (absolute com-
ponent, referred only to U
N
). The relative component for triggering the sum current
monitoring is set under address
8109
SUM.Fact. U
.
Note
In power system data 1, the voltage earth path and its matching factor
Uph / Udelta
were specified. Measured value monitorings will only function properly if the setting
there is correct.
Fuse Failure Moni-
toring
Measuring voltages failure detection will only be effective and available if address
180
FUSE FAIL MON.
is configured to
Enabled
. If the function is not required
Disabled
is set. The function can be turned
8001
or
FUSE FAIL MON.
under address
ON
OFF
.
The thresholds U
2
/U
1
≥
40 % and I
2
/I
1
≤
20% for detecting 1-pole and 2-pole voltage
failures are fixed. The thresholds for detecting a 3-pole voltage failure (undervoltage
threshold = 10 V, below which the failure detection feature responds unless the current
changes significantly and the differential current monitoring = 0.5 I
N
) are likewise fixed
and need not be set.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...