3 Mounting and Commissioning
284
7UM61 Manual
C53000-G1176-C127-3
Figure 3-21
Directional Check with Holmgreen Connection
If in an isolated network the voltage connections for the reactive current measurement
should be kept for testing, then it should be noted that for a power flow with inductive
component in forwards direction a backwards direction results (contrary to an earth
fault in this direction).
Shut down generator after completion of the directional tests. Correct connections
must be re-established and re-checked.
Spill Current
For calibration to the spill current, a three-pole short-circuit bridge that is able to with-
stand rated current is installed at the circuit breaker. Start up generator and slowly
excite until the rated machine current is reached.
Read out the operational measured value I
EE
. This measured values determines the
setting value of address
5003
3I0>
. Parameter
3I0>
should be about twice that mea-
sured value to ensure a sufficient security margin between the earth fault current used
for directional determination and the spill current. Next, check whether the protection
zone determined by the setting value
U0>
must be reduced.
Activate the stator earth fault protection: Address
5001
S/E/F PROT.
=
ON
.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...