2.35 Ancillary Functions
215
7UM61 Manual
C53000-G1176-C127-3
2.35.2.2 Information List
2.35.3 Set Points (Measured Values)
2.35.3.1 Functional Description
Limit Value Moni-
torings
SIPROTEC
®
7UM61 allows limit levels for important measured and counter values to
be set. If during operation a value transgresses one of these limits, the device gener-
ates an alarm which is displayed as an operational indication. As for all operational in-
dications, it is possible to output the information to LED and/or output relay and via in-
terfaces. In contrast to the actual protective functions, such as time-overcurrent
protection or overload protection, this monitoring program runs in the background and
may not respond promptly during a fault if the measured values change rapidly and
protective functions pick up. Moreover, since an indication is not generated until the
set limit value has been transgressed several times, these monitoring functions cannot
respond immediately before a protection trip.
With the 7UM61, only the limit value of the undercurrent protection IL< is configured
when the device is delivered from the factory. Further limit values can be configured if
No.
Information
Type of In-
formation
Comments
601
IL1 =
MW
I L1
602
IL2 =
MW
I L2
603
IL3 =
MW
I L3
605
I1 =
MW
I1 (positive sequence)
606
I2 =
MW
I2 (negative sequence)
621
UL1E=
MW
U L1-E
622
UL2E=
MW
U L2-E
623
UL3E=
MW
U L3-E
624
UL12=
MW
U L12
625
UL23=
MW
U L23
626
UL31=
MW
U L31
627
UE =
MW
Displacement voltage UE
629
U1 =
MW
U1 (positive sequence)
630
U2 =
MW
U2 (negative sequence)
641
P =
MW
P (active power)
642
Q =
MW
Q (reactive power)
644
Freq=
MW
Frequency
645
S =
MW
S (apparent power)
650
UE3h=
MW
UE 3rd harmonic
765
U/f =
MW
(U/Un) / (f/fn)
830
IEE =
MW
Senstive Earth Fault Current
831
3I0 =
MW
3I0 (zero sequence)
832
U0 =
MW
U0 (zero sequence)
901
PF =
MW
Power Factor
902
PHI =
MW
Power angle
903
R =
MW
Resistance
904
X =
MW
Reactance
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...