2 Functions
148
7UM61 Manual
C53000-G1176-C127-3
2.24.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.24.4 Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
6501
STARTUP MOTOR
OFF
ON
Block relay
OFF
Motor Starting Time Su-
pervision
6502
START. CURRENT
1A
0.10 .. 16.00 A
3.12 A
Starting Current of Motor
5A
0.50 .. 80.00 A
15.60 A
6503
STARTING TIME
1.0 .. 180.0 sec
8.5 sec
Starting Time of Motor
6504
LOCK ROTOR TIME
0.5 .. 120.0 sec;
∞
6.0 sec
Permissible Locked Rotor
Time
6505
I MOTOR START
1A
0.60 .. 10.00 A
1.60 A
Current Pickup Value of
Motor Starting
5A
3.00 .. 50.00 A
8.00 A
No.
Information
Type of In-
formation
Comments
6801
>BLK START-SUP
EM
>BLOCK Motor Starting Supervision
6805
>Rotor locked
EM
>Rotor is locked
6811
START-SUP OFF
AM
Starting time supervision switched OFF
6812
START-SUP BLK
AM
Starting time supervision is BLOCKED
6813
START-SUP ACT
AM
Starting time supervision is ACTIVE
6821
START-SUP TRIP
AM
Starting time supervision TRIP
6822
Rotor locked
AM
Rotor is LOCKED after Locked Rotor Time
6823
START-SUP PU
AM
Starting time supervision picked up
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...