A.7 Settings
381
7UM61 Manual
C53000-G1176-C127-3
1202
I>
O/C Prot. I>
1A
0.05 .. 20.00 A
1.35 A
I> Pickup
5A
0.25 .. 100.00 A
6.75 A
1203
T I>
O/C Prot. I>
0.00 .. 60.00 sec;
∞
3.00 sec
T I> Time Delay
1204
U< SEAL-IN
O/C Prot. I>
ON
OFF
OFF
State of Undervoltage Seal-in
1205
U<
O/C Prot. I>
10.0 .. 125.0 V
80.0 V
Undervoltage Seal-in Pickup
1206
T-SEAL-IN
O/C Prot. I>
0.10 .. 60.00 sec
4.00 sec
Duration of Undervoltage Seal-in
1207A
I> DOUT RATIO
O/C Prot. I>
0.90 .. 0.99
0.95
I> Drop Out Ratio
1301
O/C I>>
O/C Prot. I>>
OFF
ON
Block relay
OFF
Overcurrent Time Protection I>>
1302
I>>
O/C Prot. I>>
1A
0.05 .. 20.00 A
4.30 A
I>> Pickup
5A
0.25 .. 100.00 A
21.50 A
1303
T I>>
O/C Prot. I>>
0.00 .. 60.00 sec;
∞
0.10 sec
T I>> Time Delay
1304
Phase Direction
O/C Prot. I>>
Forward
Reverse
Reverse
Phase Direction
1305
LINE ANGLE
O/C Prot. I>>
-90 .. 90
°
60
°
Line Angle
1401
O/C Ip
O/C Prot. Ip
OFF
ON
Block relay
OFF
Inverse O/C Time Protection Ip
1402
Ip
O/C Prot. Ip
1A
0.10 .. 4.00 A
1.00 A
Ip Pickup
5A
0.50 .. 20.00 A
5.00 A
1403
T Ip
O/C Prot. Ip
0.05 .. 3.20 sec;
∞
0.50 sec
T Ip Time Dial
1404
TIME DIAL: TD
O/C Prot. Ip
0.50 .. 15.00 ;
∞
5.00
TIME DIAL: TD
1405
IEC CURVE
O/C Prot. Ip
Normal Inverse
Very Inverse
Extremely Inv.
Normal Inverse
IEC Curve
1406
ANSI CURVE
O/C Prot. Ip
Very Inverse
Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse
ANSI Curve
1407
VOLT. INFLUENCE
O/C Prot. Ip
without
Volt. controll.
Volt. restraint
without
Voltage Influence
1408
U<
O/C Prot. Ip
10.0 .. 125.0 V
75.0 V
U< Threshold for Release Ip
1601
Ther. OVER LOAD
Therm. Overload
OFF
ON
Block relay
Alarm Only
OFF
Thermal Overload Protection
1602
K-FACTOR
Therm. Overload
0.10 .. 4.00
1.11
K-Factor
1603
TIME CONSTANT
Therm. Overload
30 .. 32000 sec
600 sec
Thermal Time Constant
1604
Θ
ALARM
Therm. Overload
70 .. 100 %
90 %
Thermal Alarm Stage
1605
TEMP. RISE I
Therm. Overload
40 .. 200
°
C
100
°
C
Temperature Rise at Rated Sec.
Curr.
1606
TEMP. RISE I
Therm. Overload
104 .. 392
°
F
212
°
F
Temperature Rise at Rated Sec.
Curr.
1607
TEMP. INPUT
Therm. Overload
Disabled
Fieldbus
RTD 1
Disabled
Temperature Input
1608
TEMP. SCAL.
Therm. Overload
40 .. 300
°
C
100
°
C
Temperature for Scaling
1609
TEMP. SCAL.
Therm. Overload
104 .. 572
°
F
212
°
F
Temperature for Scaling
1610A
I ALARM
Therm. Overload
1A
0.10 .. 4.00 A
1.00 A
Current Overload Alarm Setpoint
5A
0.50 .. 20.00 A
5.00 A
1612A
K
τ
-FACTOR
Therm. Overload
1.0 .. 10.0
1.0
Kt-Factor when Motor Stops
1615A
I MAX THERM.
Therm. Overload
1A
0.50 .. 8.00 A
3.30 A
Maximum Current for Thermal
Replica
5A
2.50 .. 40.00 A
16.50 A
1616A
T EMERGENCY
Therm. Overload
10 .. 15000 sec
100 sec
Emergency Time
1701
UNBALANCE LOAD
Unbalance Load
OFF
ON
Block relay
OFF
Unbalance Load Protection
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...