4 Technical Data
324
7UM61 Manual
C53000-G1176-C127-3
4.11
Overvoltage Protection (ANSI 59)
Setting Ranges / Increments
Times
Tolerances
Influencing Variables
Measured Quantity
Maximum of the phase-to-phase voltages, calcu-
lated from the phase-to-earth voltages
Pickup thresholds U<, U<<, Up<
30.0 V to 170.0 V
Increments 0.1V
Dropout ratio RV U<
(Stages U>, U>>)
0.90 to 0.99
Increments 0.01
Time Delays T U>, T U>>
0.00 s to 60.00 s
or
∞
(ineffective)
Increments 0.01
s
The set times are pure delay times.
Pickup Times U>, U>>
approx. 50 ms
Dropout times U>, U>>
approx. 50 ms
Pickup Voltage Limits
1 % of setting value or 0.5 V
Delay times T
1 % of setting value or 10 ms
Power Supply DC Voltage in Range
0,8
≤
U
PS
/U
PSN
≤
1.15
≤
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
≤
0.5 % / 10 K
Frequency in Range
0,95
≤
f/f
N
≤
1.05
≤
1 %
Harmonics
– Up to 10 % 3rd harmonic
– Up to 10 % 5th harmonic
≤
1 %
≤
1 %
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...