background image

BISTABLE RELAY PBM-07 

MANUAL INSTRUCTION

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

plik: inst_ext_en_pbm-07 | modyfikacja: 25.01.2016

APPEARANCE

FEATURES

DESCRIPTION

● control of lighting and other devices 

according to a defined sequence,

● output status indicated by red LEDs (2 

x red LED),

● power supply indication (1 x green LED),

● system release only from the “L” line,

● possibility of cooperation with unipolar 

backlit push buttons,

● two-wire control installation,

● two independent relay outputs – (dry 

contacts) 2 NO /NC contacts with a 

maximum load of 16 A,

● mounting in distribution boards 

  (TH35 rail).

The PBM-07 bistable relay is used to con-

trol lighting or any other device by means 

of  unipolar  push  buttons  connected  in  a 

parallel  way.  The  relay  is  equipped  with 

two outputs activated by means of impuls-

es given to the (IN) input. It allows to con-

trol two circuits / branches simultaneously. 

The  control  impulse  must  be  the  “L”  line 

signal. The trigger input structure enables 

cooperation with backlit push buttons (in-

cluding  LED  backlight).  The  total  current 

of backlight for the (IN) input can not ex-

ceed 1,5 mA. The device is designed to be 

mounted in distribution boards (TH35 rail). 

LEDs  on  the  front  panel  indicate  power 

supply (green LED) and the output status 

(2 x red LED).

TECHNICAL DATA

PBM-07 

Input (supply) terminals: L, N

Nominal supply voltage: 230 V AC

Nominal supply voltage tolerance: -15 ÷ +10 %

Nominal frequency: 50 Hz

Nominal power consumption:  stand-by: 0,4 W

2 active outputs: 1,1 W

Optical signalling of relay status: 2x red LED

Release terminals:  IN, IN

Release control current: 7,5 mA

Cooperation with backlit push buttons: yes

Total current of the push button backlight:  < 1,5 mA

Minimum impulse release time:  70 ms

Output devices: 2 x relays

Relay contact parameters: NO/NC – 16 A / 250 VAC

Number of connection terminals: 10

Cross-section of connection cables:  0,2 ÷ 2,5 mm

2

Operating temperature range: -20 ÷ +45 

o

C

Operating position: free

Casing mounting:  TH35 rail

Casing protection degree: IP20

Protection class: II

Overvoltage category: II

Pollution degree: 2

Dimensions: 90 x 17,5 x 66 mm

Weight:  0,090 kg

Reference standard: PN-EN 60669-1, PN-EN 60669-2-1

PN-EN 61000-4-2,3,4,5,6,11

The device is designed for sin-

gle-phase installation and must 

be installed in accordance with 

standards  valid  in  a  particular 

country.  The  device  should  be 

connected  according  to  the  details  inc-

luded  in  this  manual  instruction.  Instal-

lation, connection and control should be 

carried out by a qualified electrician staff, 

who act in accordance with the service 

manual and the device functions. In case 

of  casing  dismantling,  the  guarantee  is 

lost  and  an  electric  shock  may  occur. 

Before  installation  make  sure  the  con-

nection cables are not under voltage. Im-

proper transport, storage, and use of the 

device  influence  its  wrong  functioning. 

It is not advisable to install the device in 

the following cases:  if any device part is 

missing or the device is damaged or de-

formed. In case of improper functioning 

of the device contact the producer.

CAUTION!

The symbol means selective 

collecting of electrical and electronic 

equipment.  

It is forbidden to put the used 

equipment together with other waste.

Input (supply) terminal (L)

PK1 (11,14,12) output relay 

terminals

PK2 (21,24,22) output relay 

terminals

Input (supply) terminal (N)

Release terminals (IN)

Power supply indicator
PK1 status indicator
PK2 status indicator