Bulletin B1867
902 MHz Wireless Relays Application Manual
Getting Started
• Plan where you will mount each receiver and transmitter.
• Avoid transmitting along a length of wall, sharp angles and large obstructions.
• Avoid mounting inside a metal enclosure.
• Typical range is 100’ line of sight.
• Link devices to each other before installing.
• All RIBs must be powered during Link.
• RIBWxxxB-EN3 is both a transmitter and a receiver.
• RIBWxxC-EN3 is only a receiver.
• Linking a RIB with another RIB puts the pair in Bi-directional mode.
• PHC Gateway Controller can also link with a RIB and be Bi-directional.
• Relay output state is saved at power loss. Relay output is restored when power is recovered.
(Exception: RIBW24B-EN3 will not save last state when powered from 24Vdc).
• Each Relay can be Linked to up to 30 transmitters of any combination.
page 1
902 MHz Model
Power Input (Vac)
Contact Rating (A)
Transmission Source
EEP
RIBW24B-EN3
24 ac/dc
20
Dry-Contact
A5-30-02
RIBW01B-EN3
120
20
Dry-Contact
A5-30-02
RIBW208-EN3
208
20
Dry-Contact
A5-30-02
RIBW240B-EN3
240
20
Dry-Contact
A5-30-02
RIBW277B-EN3
277
20
Dry-Contact
A5-30-02
RIBW01C-EN3
120
5
NA
A5-30-02
RIBW02C-EN3
208-277
5
NA
A5-30-02
WDWS-EN3
None
NA
Contact Closure
D5-00-01
WWS-EN3
None
NA
Button Press
F6-02-02
Device
EEP
PHC Gateway Controller
A5-38-08
Keycard
F6-02-02
Occupancy Sensor
A5-07-01
Compatible Devices from other Manufacturers
RIBWxxxB-EN3
RIBWxxC-EN3
WDWS-EN3
WWS-EN3