902 MHz Wireless Relays Application Manual B1867
page 4
Occupancy Detection
B. Auto On:
RIB and an Occupancy Sensor
• Relay activates when occupancy is detected and deactivates 30 minutes after last detection of occupancy.
• It may take up to 2 minutes for the RIB to respond to the Occupancy Sensor immediately following Link.
• Optional modes: Repeater (see page 4)
Occupancy Sensor Only Learn Procedure
1. Charge the Occupancy Sensor per Manufacturer’s instructions.
2. Apply power to RIB.
3. Press and hold LRN button on RIB for 1/2 second. LED will blink slowly.
4. Trigger a Teach telegram from the Occupancy Sensor per Manufacturer’s Instructions.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. Repeat steps 3-5 for additional occupancy sensors.
Continued from Page 3
Alarm Mode
• Activating Alarm Mode requires all learned contact switches, such as WDWS-EN3 or RIBWxxxB-EN3, to transmit a CLOSED telegram before relay will activate. Relay will
deactivate if any contact switch transmits an OPEN telegram.
Enabling Alarm Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to
FLASH, FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED blinks
twice
indicating
Alarm Mode is enabled.
Disabling Alarm Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH,
FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED blinks
three
times indicating
Alarm Mode is disabled.
Delay Mode
• Typically used with Hotel Room Energy Control (see page 5).
• Activating Delay Mode allows the relay to ignore
temporary
changes in switch states.
• The Delay Mode causes a delay of 0 seconds before relay will turn ON and a delay of 90 seconds before it will turn OFF. It also prevents the relay from activating following a
deactivation for 90 seconds (see Figure 4, below).
• The OFF delay allows the load to continue to run while the switch or transmitter is temporarily open. This is helpful when monitoring window and door contacts that may be
briefly opened and then closed. If the contact remains open for longer than 90 seconds the relay will deactivate.
• The ON delay prevents the relay from immediately responding to a closed contact.
• The 90 second OFF to ON delay is intended specifically for HVAC units so that they will not short cycle.
Enabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to
FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again,
to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks
twice
indicating
Delay Mode is enabled.
Disabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH,
FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to
FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks
three
times indicating
Delay Mode is disabled.
• Activating Repeater Mode allows relay to repeat signals from other EnOcean devices within range. The relay “hears” the signal and echoes it but will not respond to it unless it
has been linked to the transmitting device.
• Relay will allow a signal to be repeated up to two times.
Enabling Repeater Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold the CLR button for 3 seconds until LED blinks
twice
indicating
Repeater Mode is enabled.
Disabling Repeater Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold the CLR button for 3 seconds until LED blinks
three
times indicating
Repeater Mode is disabled.
Optional Modes
Repeater Mode
<10s
Off
On
Off
On
>10s
10s
90s
90s
90s
Wireless
Command
Relay
State