902 MHz Wireless Relays Application Manual B1867
page 5
Clearing ID’s from Memory
Global Clear (Reset to default settings)
Clears all linked devices, disables optional modes, and turns relay OFF.
Performing Global Clear
1. Press and hold CLR button on RIB for 3 seconds until LED begins slowly blinking.
a. Clear Mode will time out and exit in 30 seconds.
Single Device Clear
• Allows the user to Un-link a single transmitter from RIB receiver.
• Maintains all optional mode settings.
Performing Single Device Clear
1. Repeating the Link procedure for a currently Linked device will Un-link that device.
Energy Saving Applications
RIB with Door/Window Sensor(s) WDWS-EN3
• RIB activates with closed command from WDWS-EN3 and deactivates with open command.
• WDWS-EN3 retransmits contact state every 70-140 seconds.
• Optional modes: Repeater, Alarm, Delay (see pages 4)
WDWS-EN3 Link Procedure
1. Charge the WDWS-EN3 per Instructions provided with unit.
2. Apply power to RIB.
3. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4. Press and release Link button on WDWS-EN3 to transmit Teach telegram.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. To learn more WDWS-EN3, repeat steps 3-5.
WDWS-EN3
Keycard Switch
PTAC unit with RIBWxxxB-EN3 or RIBWxxC-EN3
in Hotel Room Energy Control Mode
RIBWxxxB-EN3 or RIBWxxC-EN3
in Momentary Mode with Keycard Switch
(Wired through J Box)
Hotel Room Energy Control
RIB with
WDWS-EN3
and a Keycard Switch
Consult factory.