![Siemens Siprotec 7UM611 Скачать руководство пользователя страница 139](http://html.mh-extra.com/html/siemens/siprotec-7um611/siprotec-7um611_manual_383128139.webp)
2.22 Sensitive Earth Fault Protection (ANSI 51GN, 64R)
139
7UM61 Manual
C53000-G1176-C127-3
Use as Earth Short-
Circuit Protection
For low-voltage machines with incorporated neutral conductor or machines with low-
impedance earthed starpoint, the time-overcurrent protection of the phase branches
already is an earth short-circuit protection, since the short-circuit current also flows
through the faulty phase. If the sensitive earth current detection nevertheless is be
used as earth short-circuit protection, an external intermediate transformer must be
employed to ensure that the thermal limit values (15 A continuous, 100 A for <10 s,
300 A for <1 s) of this measuring input are not exceeded by the short-circuit current.
2.22.3 Settings
2.22.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
5101
O/C PROT. Iee>
OFF
ON
Block relay
OFF
Sensitive Earth Current Protec-
tion
5102
IEE>
2 .. 1000 mA
10 mA
Iee> Pickup
5103
T IEE>
0.00 .. 60.00 sec;
∞
5.00 sec
T Iee> Time delay
5104
IEE>>
2 .. 1000 mA
23 mA
Iee>> Pickup
5105
T IEE>>
0.00 .. 60.00 sec;
∞
1.00 sec
T Iee>> Time Delay
5106
IEE<
1.5 .. 50.0 mA; 0
0.0 mA
Iee< Pickup (Interrupted Circuit)
No.
Information
Type of In-
formation
Comments
1202
>BLOCK IEE>>
EM
>BLOCK IEE>>
1203
>BLOCK IEE>
EM
>BLOCK IEE>
1221
IEE>> picked up
AM
IEE>> picked up
1223
IEE>> TRIP
AM
IEE>> TRIP
1224
IEE> picked up
AM
IEE> picked up
1226
IEE> TRIP
AM
IEE> TRIP
1231
>BLOCK Sens. E
EM
>BLOCK sensitiv earth current prot.
1232
IEE OFF
AM
Earth current prot. is swiched OFF
1233
IEE BLOCKED
AM
Earth current prot. is BLOCKED
1234
IEE ACTIVE
AM
Earth current prot. is ACTIVE
5396
Fail. REF Iee<
AM
Failure R/E/F protection Iee<
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...