2 Functions
152
7UM61 Manual
C53000-G1176-C127-3
The following figure shows the logic diagram for the restart inhibit.
Figure 2-54
Logic diagram of the Restart Inhibit
2.25.2 Setting Notes
General
Restart inhibit is only effective and available if address
166
RESTART INHIBIT
was
set to
Enabled
during configuration. If the function is not required
Disabled
is set.
Address
6601
RESTART INHIBIT
serves to switch the function
ON
or
OFF
or to block
only the trip command (
Block relay
).
www
. ElectricalPartManuals
. com