A Appendix
374
7UM61 Manual
C53000-G1176-C127-3
A.4.3
Binary Output
Table A-3
Output relay presettings for all devices and ordering variants
1)
Only for 7UM612
2)
Generator Circuit Breaker
3)
De-excitation
4)
Emergency Tripping
Binary Output
Short Text
Function No.
Description
BO1
Error PwrSupply
147
Error Power Supply
Fail Battery
177
Failure: Battery empty
BO2
Relay TRIP
511
Relay GENERAL TRIP command
BO3
List Empty
-
-
BO4 ... 11
List Empty
-
-
BO12
I> TRIP
1815
O/C I> TRIP
BO13
IEE> TRIP
1226
IEE> TRIP
U0> TRIP
5187
Stator earth fault: U0 stage TRIP
S/E/F TRIP
5193
Stator earth fault protection TRIP
BO14
U< TRIP
6539
Undervoltage U< TRIP
U> TRIP
6570
Overvoltage U> TRIP
U>> TRIP
6573
Overvoltage U>> TRIP
BO15
f1 TRIP
5236
f1 TRIP
f2 TRIP
5237
f2 TRIP
BO16
Exc<3 TRIP
5343
Underexc. prot. char. 3 TRIP
Exc<U<TRIP
5346
Underexc. prot. char.+Uexc< TRIP
BO17
f1 TRIP
5236
f1 TRIP
f2 TRIP
5237
f2 TRIP
I> TRIP
1815
O/C I> TRIP
U>> TRIP
6573
Overvoltage U>> TRIP
Pr TRIP
5097
Reverse power: TRIP
Pr+SV TRIP
5098
Reverse power: TRIP with stop
valve
S/E/F TRIP
5193
Stator earth fault protection TRIP
I2
Θ
TRIP
5161
Unbalanced load: TRIP of thermal
stage
Exc<3 TRIP
5343
Underexc. prot. char. 3 TRIP
Exc<U<TRIP
5346
Underexc. prot. char.+Uexc< TRIP
BO18
f2 TRIP
5237
f2 TRIP
I> TRIP
1815
O/C I> TRIP
U>> TRIP
6573
Overvoltage U>> TRIP
Pr+SV TRIP
5098
Reverse power: TRIP with stop
valve
S/E/F TRIP
5193
Stator earth fault protection TRIP
I2
Θ
TRIP
5161
Unbalanced load: TRIP of thermal
stage
Exc<3 TRIP
5343
Underexc. prot. char. 3 TRIP
Exc<U<TRIP
5346
Underexc. prot. char.+Uexc< TRIP
BO19
f2 TRIP
5237
f2 TRIP
I> TRIP
1815
O/C I> TRIP
S/E/F TRIP
5193
Stator earth fault protection TRIP
I2
Θ
TRIP
5161
Unbalanced load: TRIP of thermal
stage
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...