A.7 Settings
385
7UM61 Manual
C53000-G1176-C127-3
5106
IEE<
Sens. E Fault
1.5 .. 50.0 mA; 0
0.0 mA
Iee< Pickup (Interrupted Circuit)
5201
SEF 3rd HARM.
SEF 3.Harm.
OFF
ON
Block relay
OFF
Stator Earth Fault Protection
3rdHarm.
5202
U0 3.HARM<
SEF 3.Harm.
0.2 .. 40.0 V
1.0 V
U0 3rd Harmonic< Pickup
5203
U0 3.HARM>
SEF 3.Harm.
0.2 .. 40.0 V
2.0 V
U0 3rd Harmonic> Pickup
5204
T SEF 3. HARM.
SEF 3.Harm.
0.00 .. 60.00 sec;
∞
0.50 sec
T SEF 3rd Harmonic Time Delay
5205
P min >
SEF 3.Harm.
10 .. 100 %; 0
40 %
Release Threshold Pmin>
5206
U1 min >
SEF 3.Harm.
50.0 .. 125.0 V; 0
80.0 V
Release Threshold U1min>
6501
STARTUP MOTOR
Start Motor
OFF
ON
Block relay
OFF
Motor Starting Time Supervision
6502
START. CURRENT
Start Motor
1A
0.10 .. 16.00 A
3.12 A
Starting Current of Motor
5A
0.50 .. 80.00 A
15.60 A
6503
STARTING TIME
Start Motor
1.0 .. 180.0 sec
8.5 sec
Starting Time of Motor
6504
LOCK ROTOR TIME
Start Motor
0.5 .. 120.0 sec;
∞
6.0 sec
Permissible Locked Rotor Time
6505
I MOTOR START
Start Motor
1A
0.60 .. 10.00 A
1.60 A
Current Pickup Value of Motor
Starting
5A
3.00 .. 50.00 A
8.00 A
6601
RESTART INHIBIT
Restart Motor
OFF
ON
Block relay
OFF
Restart Inhibit for Motors
6602
IStart/IMOTnom
Restart Motor
1.5 .. 10.0
4.9
I Start / I Motor nominal
6603
T START MAX
Restart Motor
3.0 .. 320.0 sec
8.5 sec
Maximum Permissible Starting
Time
6604
T EQUAL
Restart Motor
0.0 .. 320.0 min
1.0 min
Temperature Equalization Time
6606
MAX.WARM STARTS
Restart Motor
1 .. 4
2
Permissible Number of Warm
Starts
6607
#COLD-#WARM
Restart Motor
1 .. 2
1
Number of Cold Starts - Warm
Starts
6608
K
τ
at STOP
Restart Motor
1.0 .. 100.0
5.0
Extension of Time Constant at
Stop
6609
K
τ
at RUNNING
Restart Motor
1.0 .. 100.0
2.0
Extension of Time Constant at
Running
6610
T MIN. INHIBIT
Restart Motor
0.2 .. 120.0 min
6.0 min
Minimum Restart Inhibit Time
7001
BREAKER FAILURE
Breaker Failure
OFF
ON
Block relay
OFF
Breaker Failure Protection
7002
TRIP INTERN
Breaker Failure
OFF
BO3
CFC
OFF
Start with Internal TRIP
Command
7003
CIRC. BR. I>
Breaker Failure
1A
0.04 .. 2.00 A
0.20 A
Supervision Current Pickup
5A
0.20 .. 10.00 A
1.00 A
7004
TRIP-Timer
Breaker Failure
0.06 .. 60.00 sec;
∞
0.25 sec
TRIP-Timer
7101
INADVERT. EN.
Inadvert. En.
OFF
ON
Block relay
OFF
Inadvertent Energisation
7102
I STAGE
Inadvert. En.
1A
0.1 .. 20.0 A;
∞
0.3 A
I Stage Pickup
5A
0.5 .. 100.0 A;
∞
1.5 A
7103
RELEASE U1<
Inadvert. En.
10.0 .. 125.0 V; 0
50.0 V
Release Threshold U1<
7104
PICK UP T U1<
Inadvert. En.
0.00 .. 60.00 sec;
∞
5.00 sec
Pickup Time Delay T U1<
7105
DROP OUT T U1<
Inadvert. En.
0.00 .. 60.00 sec;
∞
1.00 sec
Drop Out Time Delay T U1<
7110
FltDisp.LED/LCD
Device
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
8001
FUSE FAIL MON.
Measurem.Superv
OFF
ON
OFF
Fuse Failure Monitor
8101
MEASURE. SUPERV
Measurem.Superv
OFF
ON
OFF
Measurement Supervision
8102
BALANCE U-LIMIT
Measurem.Superv
10 .. 100 V
50 V
Voltage Threshold for Balance
Monitoring
8103
BAL. FACTOR U
Measurem.Superv
0.58 .. 0.90
0.75
Balance Factor for Voltage
Monitor
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...