![Siemens Siprotec 7UM611 Скачать руководство пользователя страница 73](http://html.mh-extra.com/html/siemens/siprotec-7um611/siprotec-7um611_manual_383128073.webp)
2.10 Unbalanced Load (Negative Sequence) Protection (ANSI 46)
73
7UM61 Manual
C53000-G1176-C127-3
Pickup Threshold /
Warning Stage
The value for
I2>
is set at Address
1702
. It is at the same time the pickup value for a
current warning stage whose delay time
T WARN
is set at address
1703
.
Example:
Negative Sequence
Factor K
If the machine manufacturer has indicated the loadability duration due to an unbal-
anced load by means of the constant K = (
I
2
/
I
N
)
2
· t, it is set directly at address
1704
FACTOR K
. The constant K is proportional to the admissible energy loss.
Conversion to Sec-
ondary Values
The factor K can be derived from the unbalanced load characteristic according to the
following figure by reading the time at point
I
2
/
I
N
= 1, corresponding to
FACTOR K
.
Example:
t
adm
= 20 s for
I
2
/
I
N
= 1
The constant K
primary
= 20 s determined in this way is valid for the machine side (pri-
mary side).
The factor K
primary
can be converted to the secondary side by means of the following
formula:
The calculated asymmetry factor K
sec
is set as
FACTOR K
at address
1704
.
Example:
I
N Mach
=
483 A
I
N CT prim
=
500 A
Factor K
primary
= 20 s
Setting value at address 1704:
Machine
I
N Mach
= 483 A
I
2 perm prim
/ I
N Mach
= 11 % permanent (salient-pole machine,
see Figure 2-18)
Current transform-
er
I
N CT prim
= 500 A
Setting value
I
2 adm.
= 11 % · (483 A/500 A) = 10.6 %
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...