2 Functions
40
7UM61 Manual
C53000-G1176-C127-3
2.5
Power System Data 2
The general protection data (
P.System Data 2
) include settings associated with all
functions rather than a specific protection or monitoring function. Parameter settings
P.System Data 2
can be switched using the setting group.
2.5.1
Functional Description
Setting Groups
In the 7UM61 relay, two independent setting groups (A and B) are possible. Whereas
setting values may vary, the selected functions of each setting group remain the same.
2.5.2
Setting Notes
General
To enter these group-specific general protection data (
P.System Data 2
), select in
the
SETTINGS
menu the
Group A
(
Parameter group A
), and in it
P.System Data
2
. The other setting group is accessible under
Group B
.
Rated Values of the
System
At addresses
1101
U PRIMARY OP.
and
1102
I PRIMARY OP.
, the primary refer-
ence voltage and reference current of the protected motor is entered. These values
are important for pickup settings. The allow the device to calculate operational values
as percentage values. For example, if a CT ratio of 500/1 is selected and the rated
current of the generator is 483 A, a value of 500 A should be entered at address
211
and a value of 483 A under
I PRIMARY OP.
. 483 amps are now displayed as 100%
in the percentage metering display.
Active Power Direc-
tion
Address
1108
ACTIVE POWER
is used to specify the active power direction in the
normal mode (
Generator
= output or
Motor
= input) or to adapt it to the power
system conditions without device recabling.
2.5.3
Settings
2.5.4
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
1101
U PRIMARY OP.
0.10 .. 400.00 kV
6.30 kV
Primary Operating Voltage
1102
I PRIMARY OP.
10 .. 50000 A
483 A
Primary Operating Current
1108
ACTIVE POWER
Generator
Motor
Generator
Measurement of Active Power for
No.
Information
Type of In-
formation
Comments
501
Relay PICKUP
AM
Relay PICKUP
511
Relay TRIP
AM
Relay GENERAL TRIP command
533
IL1:
AM
Primary fault current IL1
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...