2 Functions
130
7UM61 Manual
C53000-G1176-C127-3
Figure 2-43
Earth Fault Direction Detection with Busbar Connection
Consequently, the loading resistor must be situated on the other side of the measure-
ment location (current transformer, toroidal current transformer) viewed from the ma-
chine. The earthing transformer is preferably connected to the busbar. Apart from the
magnitude of the earth fault current, the direction of this current in relation to the dis-
placement voltage is needed for the secure detection of a machine earth fault with
busbar connection. The directional border between "machine direction" and "network
direction" can be altered in the 7UM61 (refer to following figure).
The protection then detects a machine earth fault if the following three criteria are ful-
filled:
• Displacement voltage larger than set value
U0>
,
• Earth fault current across the measurement location larger than set value
3I0>
,
• Earth fault current is flowing in the direction of the protected machine.
Figure 2-44
Characteristic of the Stator Earth Fault Protection for Busbar Connection
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...