4.17 Sensitive Earth Fault Protection (ANSI 51GN, 64R)
331
7UM61 Manual
C53000-G1176-C127-3
4.17 Sensitive Earth Fault Protection (ANSI 51GN, 64R)
Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Influencing Variables
Pickup Current I
EE
>
2 mA to 1000 mA
Increments 1 mA
Delay time T
IEE
>
0.00 s to 60.00 s
or
∞
(ineffective)
Increments 0.01 s
Pickup Current I
EE
>>
2 mA to 1000 mA
Increments 1 mA
Delay time T
IEE
>>
0.00 s to 60.00 s
or
∞
(ineffective)
Increments 0.01 s
Measuring circuit Supervision when Used as
Rotor Earth Fault Protection I
EE
<
1.5 mA to 50.0 mA or 0.0
mA (ineffective)
Increments 0.1 mA
Pickup Times
approx. 50 ms
Dropout Times
approx. 50 ms
Measuring Circuit Supervision (Delay)
approx. 2 s
Pickup currents I
EE
>, I
EE
>>
approx. 0.95 or 1 mA
Measuring Circuit Supervision I
EE
<
approx. 1.10 or 1 mA
Pickup current
1 % of setting value or 0.5 mA
Time Delay
1 % of setting value or 10 ms
Power Supply DC Voltage in Range
0,8
≤
U
PS
/U
PSN
≤
1.15
≤
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
≤
0.5 % / 10 K
Frequency in Range
0,95
≤
f/f
N
≤
1.05
≤
1 %
Harmonics
- Up to 10 % 3rd harmonic
- Up to 10 % 5th harmonic
≤
1 %
≤
1 %
Note:
For the purpose of high sensitivity, the linear range of the measuring input for the sensi-
tive ground fault acquisition is from 2 mA to 1600 mA.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...