2 Functions
100
7UM61 Manual
C53000-G1176-C127-3
The following secondary side setting value of zone 2 results at address
3310
ZONE
Z2
:
Figure 2-30
Time Grading for Machine Impedance Protection – Example
Z1B Overreach
Zone
The Z1B overreach zone (address
3308
ZONE Z1B
) is an externally controlled stage.
It does not influence the Z1 zone normal stage. Consequently there is no changeover,
but the overreach zone is enabled or disabled depending on the position of the high-
voltage side circuit breaker.
The Z1B zone is usually enabled by an opened high-voltage circuit breaker. In this
case every impedance protection pickup can only be due to a fault in the protection
zone of the block, since the power system is disconnected from the block. Conse-
quently the fast tripping zone can be extended to between 100 % and 120 % of the
protection zone without any loss of selectivity.
The Z1B zone is activated via a binary input controlled by the circuit breaker auxiliary
contact (see Figure 2-30). The overreach zone is allocated an individual
3309
T-Z1B
time delay.
Final Stage
For short circuits outside the Z1 and Z2 zones, the device functions as a time-delayed
overcurrent protection. Its nondirectional final time
T END
is selected so that its time
value overreaches the second or third stage of the series-connected network distance
protection.
www
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...