background image

 

 

Date Code 20150401 

 

SEL Application Guide 2015-12 

Application Guide 

Volume I 

AG2015-12 

Testing a Two-Terminal Application  

of the SEL-411L in Test Mode 

Ashwin Vashist and George Alexander

 

I

NTRODUCTION

 

The SEL-411L Advanced Line Differential Protection, Automation, and Control System has a 
built-in test mode with flexible single-terminal and multiterminal testing options. This mode 
allows you to perform acceptance, commissioning, and maintenance testing on a line differential 
application that uses SEL-411L Relays in an easy and efficient manner. The 

TEST 87L

 

command makes it possible to test the differential element on an in-service line from only one 
terminal or from all terminals at the same time (the latter requires the test sets to be satellite-
synchronized). 

Figure 1 shows a typical line differential protection arrangement where the exchange of local and 
remote operating data between the relays in the scheme takes place over two channels. Bay 1 
(Channel 1) uses a dedicated fiber direct connection between the two relays and a channel-based 
data synchronization method (ping pong). Bay 2 uses multiplexers to create a hot standby 
channel. This has the potential for channel asymmetry, so a time-based synchronization is used 
for Channel 2. When external time-based synchronization is used, both SEL-411L Relays must be 
connected to an external, high-precision, IEEE C37.118-compliant time source. 

This application guide is a test guide for the scenario presented in Figure 1. The goal of this guide 
is to provide the ability to test the characteristics of the differential elements in an SEL-411L and 
to provide the tools to calculate the currents to be injected into the relay to validate the 
differential scheme. 

SEL-411L

SEL-411L

Bay 1
Bay 2

Dedicated Fiber

Hot Standby 

Channel

Digital 

Multiplexer

Digital 

Multiplexer

Bay 1
Bay 2

 

Figure 1  Typical two-terminal SEL-411L application 

Содержание SEL-411L

Страница 1: ... exchange of local and remote operating data between the relays in the scheme takes place over two channels Bay 1 Channel 1 uses a dedicated fiber direct connection between the two relays and a channel based data synchronization method ping pong Bay 2 uses multiplexers to create a hot standby channel This has the potential for channel asymmetry so a time based synchronization is used for Channel 2...

Страница 2: ...gic 87TMSUP asserts when the RELAY TEST MODE pushbutton is used to place the SEL 411L in relay test mode which turns on the pushbutton LED DEFAULT PROGRAMMING AND TEST 87L MODE The SEL 411L ships from the factory programmed with the following default equations which correspond to the activation supervision of test mode and LED indications in the relay PLT04S PB4_PUL AND NOT PLT04 ACTIVATE OR LATCH...

Страница 3: ... acceptable test points without needing to worry about inhibiting 87L function Note For applications that use SEL 411L Relays with firmware older than version R108 the watchdog counters cannot be cleared from Access Level 2 You must log in to the calibration level of the relay and clear the counters with the same command i e COM 87L WD C For more information on the watchdog timer logic please see ...

Страница 4: ...e test set Multiterminal characteristic testing Use multiple test sets at multiple terminals Test sets are satellite synchronized channels are in use and currents can be ramped at all terminals SINGLE TERMINAL AND MULTITERMINAL CHARACTERISTIC TESTS In the single terminal mode you can apply both local and remote currents to one SEL 411L This allows for the simulation of independently adjustable loc...

Страница 5: ...al or Disabled S M D s 87L Element A B C Q G a Alpha Plane Security Normal or Secure N S n Ensure that relay outputs are isolated or supervised Are you sure Y N y Testing is enabled Warning Ctrl X does not exit test mode Type TEST 87L OFF to exit When testing is complete exit the 87L test mode by using the command TEST 87L OFF as follows TEST 87L OFF Exiting 87L Test Mode Note When exiting the 87L...

Страница 6: ...A Element Test Single Terminal 87LB Element Test Single Terminal 87LC Element Test Single Terminal 87LG Element Test Single Terminal 87LQ Element Test Local Current Remote Current 87TOUT IA IB 87L A Local Current Remote Current 87TOUT IB IC 87L B Local Current Remote Current 87TOUT IC IA 87L C Local Current Remote Current 87TOUT IA IB 87L Q Local Current Remote Current 87TOUT IA IB 87L G Figure 5 ...

Страница 7: ... Relay Word bit changes from 0 to 1 or drop out Relay Word bit changes from 1 to 0 as the test currents are applied Use the MET DIF command while injecting currents to look at measured quantities the validity of the test set injected quantities and the position of the operating point on the Alpha Plane The following shows an example MET DIF command output capture for a sample single terminal chara...

Страница 8: ...urrent angle at 180 degrees Step 3 Confirm that 87TOUT is deasserted Step 4 Slowly increase the local current until 87TOUT asserts The pickup value should be within 5 percent of the value calculated by 2 PICKUP I magnitude of the remote current 87LkR 2 where 87LkR is 87LPR for an 87LA 87LB or 87LC test 87LQR for an 87LQ test and 87LGR for an 87LG test Block Angle Setting Check Step 1 Connect the p...

Страница 9: ...o not apply current at any remote terminal Start with no current applied Step 2 Slowly increase the applied local current until Relay Word bit 87TOUT asserts The pickup value should be within 5 percent of the value calculated by 4 PICKUP I 87LTAPn 87LkP 4 where 87LTAPn is 87LTAPW or 87LTAPX depending on which input is under test 87LkP is 87LPP for an 87LA 87LB or 87LC test 87LQP for an 87LQ test a...

Страница 10: ... Record this angle as ANG1 Step 5 Reset the angle of the local current to 0 degrees Step 6 Rotate the angle of the local current in the clockwise direction until 87TOUT asserts Record this angle as ANG2 Step 7 Assuming that the angles are measured as 0 to 180 degrees and 0 to 180 degrees respectively check that the block angle is set within 5 percent of the angle determined by 7 87LkA ANG1 ANG2 7 ...

Страница 11: ...e appreciate your interest in SEL products and services If you have questions or comments please contact us at Schweitzer Engineering Laboratories Inc 2350 NE Hopkins Court Pullman WA 99163 5603 USA Telephone 1 509 332 1890 Fax 1 509 332 7990 www selinc com info selinc com ...

Страница 12: ... Inc All rights reserved All brand or product names appearing in this document are the trademark or registered trademark of their respective holders No SEL trademarks may be used without written permission SEL products appearing in this document may be covered by U S and Foreign patents AG2015 12 ...

Отзывы: