Chapter 8: Using the Command Line Interface
569
Changing an Outlet's Default State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of an outlet after
the PX3TS powers up.
config:#
outlet <n> stateOnDeviceStartup <option>
Variables:
<n> is the number of the outlet that you want to configure.
<option> is one of the options:
off, on, lastKnownState and
pduDefined.
Option
Description
off
Turn off the outlet.
on
Turn on the outlet.
lastKnownState Restore the outlet to the state prior to last PDU
power down.
pduDefined PDU-defined
setting.
Note: Setting the outlet's default state to an option other than
pduDefined
overrides the PDU-defined default state on that outlet. See
Setting the PDU-Defined Default Outlet State
(on page 508).
Содержание PX3TS
Страница 5: ......
Страница 16: ...Contents xvii Index 807...
Страница 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Страница 85: ...Chapter 4 Connecting External Equipment Optional 61...
Страница 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Страница 755: ...Appendix H RADIUS Configuration Illustration 731 10 Select Standard to the left of the dialog and then click Add...
Страница 756: ...Appendix H RADIUS Configuration Illustration 732 11 Select Filter Id from the list of attributes and click Add...
Страница 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Страница 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Страница 792: ...Appendix I Additional PX3TS Information 768...
Страница 816: ...Appendix I Additional PX3TS Information 792 11 To print the currently selected topic click the Print this page icon...
Страница 820: ...Appendix J Integration 796 3 Click OK...