Chapter 5: Using the PX3TS
138
3.
Press the ON button until it is completely down.
Beeper
The PX3TS includes an internal beeper to issue an audible alarm for an
overcurrent protector which is open. An overcurrent protector can be a
fuse or a circuit breaker on the PX3TS.
The beeper sounds an alarm when any overcurrent protector trips,
blows or malfunctions.
The beeper stops after all tripped overcurrent protectors have been
reset, or all blown or bad fuses are replaced with good ones.
Warning: You must power OFF the PX3TS prior to replacing a fuse, or
a personal injury or death may be caused.
Tip: To remotely check this beeper's state via the web interface, see
PDU
(on page 176).
Power Cycling the PX3TS
There is no power switch on the PX3TS device. To power cycle the PX3TS,
turn OFF
both branch circuits supplying power to the PX3TS, wait 10
seconds, and then turn on both branch circuits.
Содержание PX3TS
Страница 5: ......
Страница 16: ...Contents xvii Index 807...
Страница 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Страница 85: ...Chapter 4 Connecting External Equipment Optional 61...
Страница 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Страница 755: ...Appendix H RADIUS Configuration Illustration 731 10 Select Standard to the left of the dialog and then click Add...
Страница 756: ...Appendix H RADIUS Configuration Illustration 732 11 Select Filter Id from the list of attributes and click Add...
Страница 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Страница 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Страница 792: ...Appendix I Additional PX3TS Information 768...
Страница 816: ...Appendix I Additional PX3TS Information 792 11 To print the currently selected topic click the Print this page icon...
Страница 820: ...Appendix J Integration 796 3 Click OK...