![Raritan PX3TS Скачать руководство пользователя страница 669](http://html1.mh-extra.com/html/raritan/px3ts/px3ts_user-manual_3996566669.webp)
Chapter 8: Using the Command Line Interface
645
Restarting the PDU
This command restarts the PX3TS device. It is not a factory default reset.
To restart the PX3TS device:
1.
Ensure you have entered administrator mode and the # prompt is
displayed.
2.
Type either of the following commands to restart the PX3TS device.
#
reset unit
-- OR --
#
reset unit
/y
3.
If you entered the command without "
/y
" in Step 2, a message
appears prompting you to confirm the operation. Type y to confirm
the reset.
4.
Wait until the Username prompt appears, indicating the reset is
complete.
Note: If you are performing this command over a USB connection,
re-connect the USB cable after the reset is completed, or the CLI
communications are lost.
Resetting Active Energy Readings
You can reset either one active energy sensor or all active energy
sensors at a time to restart the energy accumulation process.
Only users with the "Admin" role assigned can reset active energy
readings.
To reset all active energy readings of the PX3TS:
#
reset activeEnergy pdu
-- OR --
#
reset activeEnergy pdu /y
To reset one inlet's active energy readings:
#
reset activeEnergy inlet <n>
-- OR --
#
reset activeEnergy inlet <n> /y
To reset one outlet's active energy readings:
#
reset activeEnergy outlet <outlet_n>
Содержание PX3TS
Страница 5: ......
Страница 16: ...Contents xvii Index 807...
Страница 83: ...Chapter 4 Connecting External Equipment Optional 59 A DPX2 sensor package A DPX sensor package...
Страница 85: ...Chapter 4 Connecting External Equipment Optional 61...
Страница 754: ...Appendix H RADIUS Configuration Illustration 730 Note If your PX3TS uses PAP then select PAP...
Страница 755: ...Appendix H RADIUS Configuration Illustration 731 10 Select Standard to the left of the dialog and then click Add...
Страница 756: ...Appendix H RADIUS Configuration Illustration 732 11 Select Filter Id from the list of attributes and click Add...
Страница 759: ...Appendix H RADIUS Configuration Illustration 735 14 The new attribute is added Click OK...
Страница 760: ...Appendix H RADIUS Configuration Illustration 736 15 Click Next to continue...
Страница 792: ...Appendix I Additional PX3TS Information 768...
Страница 816: ...Appendix I Additional PX3TS Information 792 11 To print the currently selected topic click the Print this page icon...
Страница 820: ...Appendix J Integration 796 3 Click OK...