Appendix B: Configuration or Firmware Upgrade with a USB Drive
453
7. Verify that at least 3 configuration files are created -
fwupdate.cfg
,
config.txt
and
devices.csv
. You are ready to configure or upgrade
any EMX with these files. See
Configuration or Firmware Upgrade
with a USB Drive
(on page 443).
Firmware Upgrade via USB
Firmware files are available on Raritan website's
Support page
(
http://www.raritan.com/support/
).
Note that if the firmware file used for firmware upgrade is the same as
the firmware version running on the EMX, no firmware upgrade will be
performed unless you have set the
force_update
option to true in the
"fwupdate.cfg" file. See
fwupdate.cfg
(on page 446).
To use a USB drive to upgrade the EMX:
1. Copy the configuration file "fwupdate.cfg" and an appropriate
firmware file to the root directory of the USB drive.
2. Reference the firmware file in the
image
option of the "fwupdate.cfg"
file.
3. Plug the USB drive into the USB-A port on the EMX.
4. The EMX performs the firmware upgrade. The firmware upgrade
message "FUP" is displayed on the front panel display.
Tip: You can remove the USB drive and plug it into another EMX for
firmware upgrade when the firmware upgrade message displays.
5. It may take one to five minutes to complete the firmware upgrade,
depending on your product.
6. When the firmware upgrade finishes, the front panel display indicates
the firmware upgrade result.
=-]
(happy smiley): Successful.
=-[
(sad smiley): Failed. Check the log file in the USB drive or
contact Raritan Technical Support to look into the failure cause.
Содержание EMX2-888
Страница 19: ...Chapter 1 Introduction 5 Retrieval of the link local IPv4 address See IPv4 Address on page 72...
Страница 71: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 148: ...Chapter 6 Using the Web Interface 134 LHX 20 SHX 30 LHX 40 PowerLogic PM710...
Страница 506: ...Appendix F LDAP Configuration Illustration 492 5 Click OK The EMX_Admin role is created 6 Click Close to quit the dialog...
Страница 526: ...Appendix H RADIUS Configuration Illustration 512 Note If your EMX uses PAP then select PAP...
Страница 527: ...Appendix H RADIUS Configuration Illustration 513 10 Select Standard to the left of the dialog and then click Add...
Страница 528: ...Appendix H RADIUS Configuration Illustration 514 11 Select Filter Id from the list of attributes and click Add...
Страница 531: ...Appendix H RADIUS Configuration Illustration 517 14 The new attribute is added Click OK...
Страница 532: ...Appendix H RADIUS Configuration Illustration 518 15 Click Next to continue...