Chapter 4: Connecting External Equipment (Optional)
41
For the cabling length restrictions, see
Supported Maximum DPX
Sensor Distances
(on page 45).
Warning: For proper operation, wait for 15-30 seconds between each
connection operation or each disconnection operation of
environmental sensor packages.
To connect a DPX sensor package with a factory-installed
sensor cable:
Plug the sensor cable's RJ-12 connector into the RJ-12 SENSOR
port on the EMX.
To connect a DPX differential air pressure sensor:
1. Plug one end of a Raritan-provided phone cable into the IN port of a
differential air pressure sensor.
2. Plug the other end of this phone cable into the RJ-12 SENSOR port
on the EMX.
3. If intended, connect one DPX sensor package to the OUT port of the
differential air pressure sensor. It can be any DPX sensor package,
such as a DPX-T3H1.
The EMX device
Raritan differential air pressure sensors
One DPX sensor package (optional)
Содержание EMX2-888
Страница 19: ...Chapter 1 Introduction 5 Retrieval of the link local IPv4 address See IPv4 Address on page 72...
Страница 71: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 148: ...Chapter 6 Using the Web Interface 134 LHX 20 SHX 30 LHX 40 PowerLogic PM710...
Страница 506: ...Appendix F LDAP Configuration Illustration 492 5 Click OK The EMX_Admin role is created 6 Click Close to quit the dialog...
Страница 526: ...Appendix H RADIUS Configuration Illustration 512 Note If your EMX uses PAP then select PAP...
Страница 527: ...Appendix H RADIUS Configuration Illustration 513 10 Select Standard to the left of the dialog and then click Add...
Страница 528: ...Appendix H RADIUS Configuration Illustration 514 11 Select Filter Id from the list of attributes and click Add...
Страница 531: ...Appendix H RADIUS Configuration Illustration 517 14 The new attribute is added Click OK...
Страница 532: ...Appendix H RADIUS Configuration Illustration 518 15 Click Next to continue...