Chapter 8: Using the Command Line Interface
413
config:#
defaultThresholds <sensor type> lowerWarning <value>
Set the Default Deassertion Hysteresis for a specific sensor
type:
config:#
defaultThresholds <sensor type> hysteresis <hy_value>
Set the Default Assertion Timeout for a specific sensor type:
config:#
defaultThresholds <sensor type> assertionTimeout <as_value>
Variables:
<sensor type> is one of the following numeric sensor types:
Sensor types
Description
absoluteHumidity
Absolute humidity sensors
relativeHumidity Relative humidity sensors
temperature Temperature
sensors
airPressure
Air pressure sensors
airFlow
Air flow sensors
vibration Vibration
sensors
<value> is the value for the specified threshold of the specified
sensor type. Note that diverse sensor types use different
measurement units.
Sensor types
Measurement units
absoluteHumidity
g/m^3 (that is, g/m
3
)
relativeHumidity %
temperature
Degrees Celsius (
) or Fahrenheit ( ),
depending on your measurement unit settings.
airPressure
Pascal (Pa) or psi, depending on your
measurement unit settings.
airFlow m/s
vibration g
<hy_value> is the deassertion hysteresis value applied to the
specified sensor type.
<as_value> is the assertion timeout value applied to the specified
sensor type. It ranges from 0 to 100 (samples).
Содержание EMX2-888
Страница 19: ...Chapter 1 Introduction 5 Retrieval of the link local IPv4 address See IPv4 Address on page 72...
Страница 71: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 148: ...Chapter 6 Using the Web Interface 134 LHX 20 SHX 30 LHX 40 PowerLogic PM710...
Страница 506: ...Appendix F LDAP Configuration Illustration 492 5 Click OK The EMX_Admin role is created 6 Click Close to quit the dialog...
Страница 526: ...Appendix H RADIUS Configuration Illustration 512 Note If your EMX uses PAP then select PAP...
Страница 527: ...Appendix H RADIUS Configuration Illustration 513 10 Select Standard to the left of the dialog and then click Add...
Страница 528: ...Appendix H RADIUS Configuration Illustration 514 11 Select Filter Id from the list of attributes and click Add...
Страница 531: ...Appendix H RADIUS Configuration Illustration 517 14 The new attribute is added Click OK...
Страница 532: ...Appendix H RADIUS Configuration Illustration 518 15 Click Next to continue...