Chapter 6: Using the Web Interface
124
Changing Telnet Settings
You can enable or disable the Telnet access to the command line
interface, or change the default TCP port for the Telnet service.
To change Telnet service settings:
1. Choose Device Settings > Network Services > Telnet. The Telnet
Settings dialog appears.
2. To use a different port, type a new port number in the port field. Valid
range is 1 to 65535.
3. To enable the Telnet application, select the Enable Telnet Access
checkbox. To disable it, deselect the checkbox.
4. Click
OK.
Changing Modbus/TCP Settings
You can enable or disable the Modbus/TCP access to the EMX or the
read-only mode, or change the default TCP port for the Modbus service.
To change the Modbus service settings:
1. Choose Device Settings > Network Services > Modbus. The Modbus
Settings dialog appears.
2. To enable the Modbus/TCP access, select the Enable Modbus/TCP
Access checkbox. To disable it, deselect the checkbox.
3. To use a different port, type a new port number in the port field. Valid
range is 1 to 65535.
4. To enable the Modbus read-only mode, select the "Enable read-only
mode" checkbox. To disable it, deselect the checkbox.
Enabling the Modbus Gateway
With the Modbus Gateway feature enabled, the EMX allows Modbus
TCP clients on your network to communicate with the Modbus RTU
devices connected to the EMX.
To use the Modbus Gateway feature:
1. Connect a Modbus RTU device, or a Modbus bus with multiple RTU
devices, to the EMX via two adapters described below.
a. Connect an isolated RS485-to-RS232 adapter to the Modbus
RTU device or Modbus bus.
b. Connect an RS232-to-USB adapter (using FTDI's FT232 chip) to
the RS485-to-RS232 adapter.
Содержание EMX2-888
Страница 19: ...Chapter 1 Introduction 5 Retrieval of the link local IPv4 address See IPv4 Address on page 72...
Страница 71: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 148: ...Chapter 6 Using the Web Interface 134 LHX 20 SHX 30 LHX 40 PowerLogic PM710...
Страница 506: ...Appendix F LDAP Configuration Illustration 492 5 Click OK The EMX_Admin role is created 6 Click Close to quit the dialog...
Страница 526: ...Appendix H RADIUS Configuration Illustration 512 Note If your EMX uses PAP then select PAP...
Страница 527: ...Appendix H RADIUS Configuration Illustration 513 10 Select Standard to the left of the dialog and then click Add...
Страница 528: ...Appendix H RADIUS Configuration Illustration 514 11 Select Filter Id from the list of attributes and click Add...
Страница 531: ...Appendix H RADIUS Configuration Illustration 517 14 The new attribute is added Click OK...
Страница 532: ...Appendix H RADIUS Configuration Illustration 518 15 Click Next to continue...