Chapter 5: Using the EMX
81
6. Tighten the two screws on two sides of the module to secure it.
EMX2-888 Contact Closure Sensor LEDs
Two LEDs that show the states of corresponding CC sensor channels
are located on the leftmost of the EMX2-888 panel.
The upper LED is for CC2.
The lower LED is for CC1.
The LED is lit when the associated detector/switch enters the "alarmed"
state.
The meaning of a lit LED varies depending on the Normal state settings.
When the Normal state is set to Normally Closed (N.C):
LED
Sensor state
Off Closed
Lit Open
When the Normal state is set to Normally Open (N.O):
LED
Sensor state
Off Open
Lit Closed