Chapter 4: Connecting External Equipment (Optional)
40
Model
Supported maximum number of sensors/actuators
EMX2-111
This model has only one SENSOR port so it can manage up to 32
sensors and/or actuators.
EMX2-888
This model has 8 SENSOR ports, which can manage up to 128
sensors and/or actuators in total.
In addition, it has two built-in contact closure terminals to connect two
contact closure sensors. Therefore, the total number of sensors and
actuators it supports is 130.
For information on connecting different types of sensor packages, see:
DPX Sensor Packages
(on page 40)
DPX2 Sensor Packages
(on page 46)
DPX3 Sensor Packages
(on page 48)
DX Sensor Packages
(on page 51)
DPX Sensor Packages
Most DPX sensor packages come with a factory-installed sensor cable,
whose sensor connector is RJ-12.
Содержание EMX2-888
Страница 19: ...Chapter 1 Introduction 5 Retrieval of the link local IPv4 address See IPv4 Address on page 72...
Страница 71: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 148: ...Chapter 6 Using the Web Interface 134 LHX 20 SHX 30 LHX 40 PowerLogic PM710...
Страница 506: ...Appendix F LDAP Configuration Illustration 492 5 Click OK The EMX_Admin role is created 6 Click Close to quit the dialog...
Страница 526: ...Appendix H RADIUS Configuration Illustration 512 Note If your EMX uses PAP then select PAP...
Страница 527: ...Appendix H RADIUS Configuration Illustration 513 10 Select Standard to the left of the dialog and then click Add...
Страница 528: ...Appendix H RADIUS Configuration Illustration 514 11 Select Filter Id from the list of attributes and click Add...
Страница 531: ...Appendix H RADIUS Configuration Illustration 517 14 The new attribute is added Click OK...
Страница 532: ...Appendix H RADIUS Configuration Illustration 518 15 Click Next to continue...