Power On the Server
When AC power is applied to the server power inlets, the server boots into standby
power mode. For information, see
“Server Boot Process and Normal Operating State
.
7.
Verify that none of the server Service Action Required indicators on externally
facing indicator panels are lit.
Note -
After replacing some components, you must clear the fault in Oracle ILOM to clear fault
indicators. For details, see
“Clear Hardware Fault Messages (Oracle ILOM)” on page 53
.
8.
Power on the server.
Next Steps
■
“Power On the Server” on page 238
Power On the Server
When AC power is applied to the server power inlets, the server boots into standby
power mode. For information, see
“Server Boot Process and Normal Operating State
.
Use the following procedure to reapply main power for all server components.
1.
Ensure that the server is in standby power mode.
2.
To power on the server, do one of the following:
■
From the front of the server, press and immediately release the Power
button on the server front panel.
■
From the Oracle ILOM web interface Summary (home) screen, click
Power
State Turn On
button.
■
From the Oracle ILOM command-line interface (CLI), type:
start /System
Note -
When the server powers on, the power-on self-test (POST) can take several minutes to
complete.
238
Oracle Server X7-8 Service Manual • October 2017
Содержание X7-8
Страница 1: ...Oracle Server X7 8 Service Manual Part No E71936 01 October 2017 ...
Страница 2: ......
Страница 13: ...Contents Index 303 13 ...
Страница 14: ...14 Oracle Server X7 8 Service Manual October 2017 ...
Страница 16: ...16 Oracle Server X7 8 Service Manual October 2017 ...
Страница 46: ...46 Oracle Server X7 8 Service Manual October 2017 ...
Страница 268: ...268 Oracle Server X7 8 Service Manual October 2017 ...
Страница 294: ...294 Oracle Server X7 8 Service Manual October 2017 ...