3 - 6 3 - 6
MELSEC
3 SPECIFICATIONS
3.2.2 Maximum overall cable distance (for Ver.1.00)
The relationship between the transmission speed and the maximum overall cable
distance is described below:
(1) For a system consisting of only remote I/O stations and remote
device stations
Maximum overall cable distance
Remote I/O station
or remote
device station
Master station
Remote I/O station
or remote
device station
Remote I/O station
or remote
device station
Remote I/O station
or remote
device station
2
2
1
1
1: Cable length between remote I/O stations or remote device stations.
2: Cable length between the master station and the adjacent stations.
CC-Link dedicated cable (uses terminal resistor 110
)
Transmission rate
Station-to-station cable length
Maximum overall cable distance
1
2
156 kbps
30 cm (11.81 in.) or more
1 m (3.28 ft.) or more
1200 m (3937.2 ft.)
625 kbps
600 m (1968.6 ft.)
2.5 Mbps
200 m (656.2 ft.)
5 Mbps
30 cm (11.81 in.) to
59 cm (23.23 in.)
3
110 m (360.9 ft.)
60 cm (23.62 in.) or more 150
m
(492.15 ft.)
10 Mbps
30 cm (11.81 in.) to
59 cm (23.23 in.)
3
50 m (164.1 ft.)
60 cm (23.62 in.) to
99 cm (38.98 in.)
3
80 m (262.5 ft.)
1 m (3.28 ft.) or more
100 m (328.1 ft.)
CC-Link dedicated high performance cable (uses terminal resistor 130
)
Transmission rate
Station-to-station cable length
Maximum overall cable distance
1
2
156 kbps
30 cm (11.81 in.) or more
1 m (3.28 ft.) or more
1200 m (3937.2 ft.)
625 kbps
900 m (2952.9 ft.)
2.5 Mbps
400 m (1312.4 ft.)
5 Mbps
160 m (524.96 ft.)
10 Mbps
Number of connected
stations: 1 to 32
100 m (328.1 ft.)
Number of connected
stations: 33 to 48
30 cm (11.81 in.) to
39 cm (15.35 in.)
3
80 m (262.5 ft.)
40 cm (15.75 in.) or more 100
m
(328.1 ft.)
Number of connected
stations: 49 to 64
30 cm (11.81 in.) to
39 cm (15.35 in.)
3
20 m (65.52 ft.)
40 cm (15.75 in.) to
69 cm (27.17 in.)
3
30 m (98.43 ft.)
70 cm (27.56 in.) or more 100
m
(328.1 ft.)
3: The cable length between remote I/O stations or remote device stations is within this
range and if even one location is wired, the maximum overall cable distance will be
as indicated above.
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......