5 PROCEDURE BEFORE STARTING THE DATA LINK
5.4 Wiring
This section explains the cable wiring and precautions.
The following shows the wiring procedure.
Start
↓
Power OFF
Power OFF the personal computer.
↓
Wire the cables
Wire the network cables to the terminal block.
↓
Install the terminal block
If the terminal block has been removed for wiring, install the
terminal block.
• • • Section 5.4.2 (1) Mounting and removing
a terminal block
↓
Power ON
Power ON the personal computer.
↓
End
5.4.1 Preparation before wiring
Before wiring, check the cables and terminating resistors to be used.
(1) Cables that can be used
The following cables can be used:
• Ver.1.10-compatible CC-Link dedicated cable
• CC-Link dedicated cable (Ver.1.00-compatible)
• CC-Link dedicated high-performance cable (Ver.1.00-compatible)
These cables cannot be used together. If used, normal data transmission is not
guaranteed.
(2) The order of connecting the cables
The cables do not have to be connected in the order of station number.
(3) Terminating resistors to be used
Connect the terminating resistors included with the stations at both ends of the
stations in the CC-Link system.
The terminating resistors to be used vary depending on the cable.
Cable type
Terminating resistor to be used
Ver.1.10-compatible CC-Link dedicated cable
110
Ω
1/2W (Brown-Brown-Brown)
CC-Link dedicated cable (Ver.1.00-compatible)
CC-Link dedicated high-performance cable
(Ver.1.00-compatible)
130
Ω
1/2W (Brown-Orange-Brown)
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......