3 - 3 3 - 3
MELSEC
3 SPECIFICATIONS
1: The link points shown above apply to the use in the remote net ver.1 mode.
Refer to Table 3.2 for those in the remote net ver.2 mode, remote additional mode.
2: Ver.1.10-compatible CC-Link dedicated cables, CC-Link dedicated cables (Ver.1.00) and CC-Link dedicated high-
performance cables cannot be used together. If used together, correct data transmission will not be guaranteed.
Also attach the terminating resister which matches the kind of the cable. (Refer to Section 5.4.1)
3: Using the CC-Link Ver.2 board and the CC-Link Ver.1 board in the same computer is not allowed.
Table 3.2 Number of link points for remote net ver.2 mode/remote net additional mode
Item Specifications
Maximum No. of link points per system
Remote I/O (RX, RY) : 8192 points
Remote register (RWw) : 2048 points (master station remote device
station/local station/intelligent device
station/standby master station)
Remote register (RWr) : 2048 points (remote device station/local
station/intelligent device station/standby
master station master station)
No. of link points
per station
Expanded cyclic setting
Single
Double
Quadruple
Octuple
Remote I/O (RX, RY)
32 points
(30 points for
local station)
32 points
(30 points for
local station)
64 points
(62 points for
local station)
128 points
(126 points for
local station)
Remote register (RWw)
4 points
8 points
16 points
32 points
Remote register (RWr)
4 points
8 points
16 points
32 points
Number of link
points per
occupied station
count
Occupies
1 station
Remote I/O
(RX, RY)
32 points
32 points
64 points
128 points
Remote register
(RWw)
4 points
8 points
16 points
32 points
Remote register
(RWr)
4 points
8 points
16 points
32 points
Occupies
2 stations
Remote I/O
(RX, RY)
64 points
96 points
192 points
384 points
Remote register
(RWw)
8 points
16 points
32 points
64 points
Remote register
(RWr)
8 points
16 points
32 points
64 points
Occupies
3 stations
Remote I/O
(RX, RY)
96 points
160 points
320 points
640 points
Remote register
(RWw)
12 points
24 points
48 points
96 points
Remote register
(RWr)
12 points
24 points
48 points
96 points
Occupies
4 stations
Remote I/O
(RX, RY)
128 points
224 points
448 points
896 points
Remote register
(RWw)
16 points
32 points
64 points
128 points
Remote register
(RWr)
16 points
32 points
64 points
128 points
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......