12 - 6 12 - 6
MELSEC
12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL
STATIONS
(Master station)
(Local station)
User Program
CC-Link Ver.2
Board
CC-Link Ver.2
Board
User Program
2) Reads out the remote input (RX0) of the
CC-Link Ver.2 board on the master
station.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x1 (own station RX)
Device No.=0x0
3) Turnr ON the remote output (RY0) of
the CC-Link Ver.2 board on the master
station with the read out remote input
(RX0) ON.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x2 (own station RY)
Device No.=0x0
6) Reads out the remote register (RWr0)
of the CC-Link Ver.2 board on the
master station.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x25 (own station RWr)
Device No.=0x0
1) Turn ON the remote output (RY0) of the
CC-Link Ver.2 board on the local station.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x2 (own station RY)
Device No.=0x0
4) Reads out the remote input (RX0) of the
CC-Link Ver.2 board on the local station.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x1 (own station RX)
Device No.=0x0
5) Writes 0x5555 to the remote register
(RWw0) of the CC-Link Ver.2 board on
the local station with the read out remote
input register (RX0)ON.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x24 (own station RWw)
Device No.=0x0
8) Reads out the remote register (RWr0) of
the CC-Link Ver.2 board on the local
station.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x25 (own station RWr)
Device No.=0x0
7) Writes 0xAAAA to the remote register
(RWw0) of the CC-Link Ver.2 board on
the master station if the read out remote
register (RWr0) is 0x5555.
Arguments to be set:
Station No.=0xFF (own station)
Device type=0x24 (own station RWw)
Device No.=0x0
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......