12 - 12 12 - 12
MELSEC
12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL
STATIONS
12.2.3 Setting the local station
The following shows the local station setting.
(1) Switch setting (channel No. setting)
The channel No. for the CC-Link Ver.2 board is set to 81 as an example in this
section.
For the setting, refer to Section 12.2.2 (1).
(2) Parameter settings
The following shows the local station’s parameter settings by the CC-Link Ver.2
Utility.
<Parameter settings screen>
<Other settings screen>
1)
3)
4)
7)
6)
5)
2)
8)
9)
10)
(a) Parameter settings
The following shows the parameter setting values. The parameter setting
check list and the station information setting check list in Appendix can be
used for the setting.
Table 12.3 Parameter Setting Check List
Setting item
Setting range/Item
1) Channel No.
Channel No. 81 / Channel No.82
Channel No. 83 / Channel No.84
2) Sta. No./Type
No.1
Master station / Local station / Standby master station
3) Transmission rate
156kbps / 625kbps / 2.5Mbps / 5Mbps / 10Mbps
4) Mode
Remote net [Ver.1 mode] / Remote net [Ver.2 mode]
Remote net [Additional mode] / Off line
Operational
settings
5) Expanded cyclic
single / double / quadruple / octuple
6) Occupied Sta.
Occupies 1 station / Occupies 2 stations
Occupies 3 stations / Occupies 4 stations
7) Input for Err. Sta.
Hold / Clear
Other settings
Retry count
3 Times
Automatic reconnection
station count
1 Modules
Standby master station No.
No.0
Delay information setting
0 50 micro sec
8) Driver WDT Monitoring Time
No setting / 8 ms
9) Block data assurance perz
station
Disable / Enable
10) Link refresh cycle
No setting / ms
Station information
settings
All connect count
Modules
1: Set station No.5 to the Ver.2 Intelligent device station.
2: Set Remote net [Ver.2 mode] to the Ver.2 intelligent device stations.
3: Set "double" and "occupied 2 stations" to the Ver.2 intelligent device station.
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......