App - 20 App - 20
MELSEC
APPENDIX
Number Name
Description
Availability
( : Available, : Not available)
Online
Offline
Master
station
Local
station
SB0065
(5E6
H
, b5)
Input data status of
host data link faulty
station
Indicates the input status setting from a data link faulty station of
the host.
OFF: Clear
ON : Hold
SB0066
(5E6
H
, b6)
Number of host
occupied stations
Indicates the setting status of host occupied stations.
Number of occupied station
SB0066
SB0067
1 station
OFF
OFF
2 stations
OFF
ON
SB0067
(5E6
H
, b7)
3 stations
ON
ON
4 stations
ON
OFF
SB006A
(5E6
H
, b10)
Switch setting status
Indicates the setting status of the host.
OFF: Normal
ON : Setting error exists (the error code is stored in SW006A)
SB006D
(5E6
H
, b13)
Parameter setting
status
Indicates the parameter setting status.
OFF: Normal
ON : Setting error exists (the error code is stored in SW0068)
SB006E
(5E6
H
, b14)
Host station
operation status
Indicates the host data link operation status.
OFF: Being executed
ON : Not executed
SB0070
(5E7
H
, b0)
Master station
information
Indicates the data link status.
OFF: Data link control by the master station
ON : Data link control by the standby master station
SB0071
(5E7
H
, b1)
Standby master
station information
Indicates whether or not a standby master station is present.
OFF: Not present
ON : Present
SB0072
(5E7
H
, b2)
Scan mode setting
information
Indicates the scan mode setting information.
OFF: Asynchronous mode
ON : Synchronous mode
SB0073
(5E7
H
, b3)
Operation
specification when
CPU is down status
Indicates the operation specification status using a parameter
when the CPU is down.
OFF: Stop
ON : Continue
SB0074
(5E7
H
, b4)
Reserved station
specified status
Indicates the reserved station specification status using a
parameter.
OFF: No specification
ON : Specification exists (information is stored in SW0074 to
SW0077)
SB0075
(5E7
H
, b5)
Error invalid station
specified status
Indicates the error invalid station specification status using a
parameter.
OFF: No specification
ON : Specification exists (information is stored in SW0078 to
SW007B)
SB0076
(5E7
H
, b6)
Temporary error
invalid station setting
information
Indicates whether there is a temporary error invalid station setting.
OFF: No setting
ON : Setting exists (information is stored in SW007C to
SW007F)
SB0077
(5E7
H
, b7)
Parameter receive
status
Indicates the parameter receive status from the master station.
OFF: Reception complete
ON : Reception not complete
SB0079
(5E7
H
, b9)
Master station return
specification
information
Indicates whether the "Type" setting of the host operates is set to
"Master station" or "Master station (Duplex function)."
OFF: Master station
ON : Master station (Duplex function)
SB007B
(5E7
H
, b11)
Host master/standby
master operation
status
Indicates whether the host operates as the master or standby
master station.
OFF: Operates as the master station (controlling data link)
ON : Operates as the standby master station (standby)
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......