App - 24 App - 24
MELSEC
APPENDIX
Number Name
Description
Availability
( : Available, : Not available)
Online
Offline
Master
station
Local
station
SW005F
(65F
H
)
Remote device
station
initialization
procedure
registration
instruction result
Stores the execution result of the initialization procedure registration
instruction with SB000B.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
3
SW0060
(660
H
)
Mode setting
status
Stores the mode setting status.
0: Online (with automatic return)
2: Offline
3: Line test 1
4: Line test 2
6: Hardware test
SW0061
(661
H
)
Host station
number
Stores the station number of the host that is currently in operation.
0 :
Master
station
1 to 64 : Local station
SW0062
(662
H
)
Module operating
status
Stores the operation setting status of the CC-Link Ver.2 board.
Input status from the data
link faulty station
0: Clear
1: Hold
Master station duplex function
0: Master station duplex function invalid
1: Master station duplex function valid
Number of occupied stations
00: Occupies 1 station
10: Occupies 2 stations
11: Occupies 3 stations
01: Occupies 4 stations
Slave station refresh/forced clear
setting in case of programmable
controller CPU STOP
0: Refresh
1: Clears compulsorily
Expanded cyclic setting
00: single
01: double
10: quadruple
11: octuple
0
b15
b
12
b
11
b
10
b
9
0
0
0
b8 b7 b6 b5 b4 b3 b2 b1 b0
0
to
0
Station type
0: Master station/local station
1: Standby master station
(Valid only when b1 is 0)
SW0064
(664
H
)
No. of retries
information
Indicates the retry count setting information when there is an error
response.
1 to 7 (times)
SW0065
(665
H
)
No. of automatic
return stations
Indicates the setting information for the number of automatic return
stations during one link scan.
1 to 10 (stations)
SW0066
(666
H
)
Delay timer
information
Indicates the setting information for the scan interval delay time.
0 to 100 (50
s)
SW0067
(667
H
)
Parameter
information
Stores the parameter information area to be used.
0
H
: CPU built-in parameters
3
H
: Dedicated instruction (parameter setting with the RLPASET
instruction and data link startup.)
D
H
: Default parameters (automatically starts CC-Link)
SW0068
(668
H
)
Host parameter
status
Stores the parameter setting status.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
3: Can be used for the master station only.
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......