6 - 11 6 - 11
MELSEC
6 PARAMETER SETTINGS
6.5 Status Difference Between a Master Station and a Slave Station at an Error
The status at an error occurrence differs depending on the settings of "Input for Err.
Sta" in "Operational settings" of Parameter.
When configuring the settings, consider the station status at errors listed below.
(1) Status of a master station and remote I/O station
The following table shows the status of the master station and remote I/O
stations when an error occurred.
Data link status
Master station
Remote I/O station
Remote input
(RX)
Remote
output
(RY)
Remote
register
(RWw)
Remote register
(RWr)
Input Output
When the local station's programmable controller CPU is
stopped
(data link continues)
All points are set to off
for only the receive
area from the stopped
local station
1
Continue
Continue
Continue Continue
Continue
When data link for
the entire system is
stopped
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear Clear
— — Latch —
All points
off
Hold Latch
When a
communication error
(power off, etc.)
occurs in a remote
I/O station
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear
Clears the receive
area from the remote
I/O station having a
communication error
Continue
Continue
Continue
—
All points
off
Hold
Retains the receive
area from the remote
I/O station having a
communication error
When a
communication error
(power off, etc.)
occurs in a remote
device station
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear
Clears the receive
area from the remote
device station having
a communication error
Continue
Continue
Retains the
receive area
from the remote
device station
having a
communication
error
Continue
Continue
Hold
Retains the receive
area from the remote
device station having
a communication error
When a
communication error
(power off, etc.)
occurs in a local
station
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear
Clears the receive
area from the local
station having a
communication error
Continue
Continue
Retains the
receive area
from the local
station having a
communication
error
Continue
Continue
Hold
Retains the receive
area from the local
station having a
communication error
1: This is because Yn0 (refresh direction) is turned off.
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......