13 - 6 13 - 6
MELSEC
13 COMMUNICATION BETWEEN THE MASTER STATION AND
INTELLIGENT DEVICE STATION (AJ65BT-R2)
User Program
CC-Link Ver.2 Board
1) Writes the initial setting values for transmission/
reception to the buffer memory on the AJ65BT-R2.
Arguments to be set:
Word/byte unit designation=0
Transmission area head address designation=200H
Transmission area size designation=200H
Reception area head address designation=400H
Reception area size designation=200H
Transmission timeout time designation=0
2) Turns ON the initialization request signal (RY4).
3) Turns ON the initialization request signal (RY4)
of the AJ65BT-R2.
4) If the initialization of the AJ65BT-R2 is normal,
the initialization normal complete signal (RX4)
turns ON. If not, the initialization error complete
signal (RX5) turns ON.
5) Reads out the initialization normal complete signal
(RX4).
6) With the initialization normal complete signal (RX4)
ON, the initialization request signal (RY4) is turned
OFF.
7) Turns OFF the initialization request signal
(RY4).
8) The AJ65BT-R2 turns OFF the initialization
normal complete signal (RX4) and the
initialization error complete signal (RX5).
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......