6 - 4 6 - 4
MELSEC
6 PARAMETER SETTINGS
Table 6.2 Availability of station information setting (only when selecting the master station)
: Setting required : Setting not required
Setting item
Mode setting
Number of
connected
modules
Station type
Expanded
cyclic
Occupied
Sta.
Remote station
points
Reserve/
invalid
station
count
Intelligent
buffer
select
(word)
Remote net ver.1
mode
No setting
Remote I/O station
Remote device station
Intelligent device station
Remote net ver.2
mode
No setting
2
Ver.1 Remote I/O station
0 points
(Reserved station)
8 points
8
8 empty points
16 points
32 points
Ver.1 Remote device station
2
Ver.1 Intelligent device station
2
Ver.2 Remote device station
2
Ver.2 Intelligent device station
2
Remote net
additional mode
1
No setting
Ver.1 Remote I/O station
Ver.1 Remote device station
Ver.1 Intelligent device station
Ver.2 Remote device station
Ver.2 Intelligent device station
1: Set smaller station numbers to the remote net ver.1 mode stations and larger station numbers to the remote net ver.2
mode stations.
System configuration with remote net ver.1 mode stations only is available while system configuration with remote net
ver.2 mode stations only is not allowed.
2: The following table shows the remote station points setting options available for the expanded cyclic setting and the
occupied station count.
Table 6.3 Remote station points setting options
Station type
Expanded
cyclic
Occupied station count
No setting
Occupies 1
station
Occupies 2
stations
Occupies 3
stations
Occupies 4
stations
No setting
Ver.1 remote device
Ver.1 intelligent device
Single
(fixation)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
32 points
32 points
64 points
96 points
128 points
Ver.2 remote device
Ver.2 intelligent device
Single
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
32 points
32 points
64 points
96 points
128 points
Double
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
32 points
32 points
96 points
160 points
224 points
Quadruple
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
64 points
64 points
192 points
320 points
448 points
Octuple
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
0 points
(Reserved
station)
128 points
128 points
384 points
640 points
896 points
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......